Accuracy |
: |
0.25% F.S.
(23+5oC) |
 |
Temp.
coefficient |
: |
100ppm/oC
(0-50oC) |
 |
Input burden |
: |
<0.2VA
(voltage)
<0.2VA (current) |
 |
Maximum
input over |
: |
Current
related input: 3 x rated continuous, 10 x rated 30 sec, 25 x rated 3 sec, 50 x rated 1sec
Voltage related input: maximum 2 x rated continuous) |
 |
Response
time |
: |
<250ms
(0-90%) |
 |
Output
ripple (p-p) |
: |
<0.1%
F.S. |
 |
Output
of WH or VarH |
: |
Open
collector type, max. 50V/30mA |
 |
Dielectric
strength |
: |
2KVac/1
min. (input/output/ aux. power/case) |
 |
Surge test |
: |
ANSI
C37.90a/1974, DIN-IEC 255-4 impulse voltage 5KV (1.2 x 50ms) |
 |
Operating
condition |
: |
0~55oC
(20 to 95% RH non-condensed) |
 |
Storage
condition |
: |
0~70oC
(20 to 95% RH non-condensed) |
 |
Power supply |
: |
AC
110V/220V + 20% (50/60Hz) < 3.5VA
(Optional DC 48V or DC 110V + 20%) |